Field Setting
[2] Automatic setback function
First
code
2
Setback function provides the possibility to lower the room temperature. The setback function
can for instance be activated during the night because the temperature demands during night
and day are not the same.
Notes :
1. By default the setback function is enabled, if it's not needed, it should be disabled.
2. The setback function can be combined with the automatic weather dependent set point
3. Setback function is an automatic daily scheduled function.
4. It is advised to set the start time of automatic storage during night [1-01] on the moment that
* Setback operation for room temperature control
[5-03] 18°C
* Setback operation for leaving water control
A
B
Notes :
1. In setback operation for room temperature control, immediately a setback temperature is
2. In setback operation for leaving water control, a shift down value is chosen. This value
90
Second
code
Setting name
Automatic setback function
00
Status: setback operation
01
Setback operation start time
02
Setback operation stop time
operation.
the setback function starts [2-01].
[2-00] Status: defines whether the setback function is turned ON (1) or OFF (0)
[2-01] Start time: time at which setback is started
[2-02] Stop time: time at which setback is stopped
T
A
21°C
[2-01]
A
Normal room temperature set point
t
Time
T
Temperature
[5-03]
Room setback temperature (actual temperature)
T
65°C
5°C [5-02]
60°C
[2-01]
A
Normal leaving water temperature set point
B
Leaving water setback temperature
t
Time
T
Temperature
[5-02]
Leaving water setback value (shift value)
set.
should be lowered from the normal set point.
t
[2-02]
t
[2-02]
Default
value
Range
Step
1 (ON)
0/1
23:00
0:00~23:00
1:00
5:00
0:00~23:00
1:00
Test Operation
ESIE09-08
Unit
hour
hour