ESIE09-08
[5] Automatic setback and disinfection set point
First
code
5
See also "[4] Disinfection function" on page 92 for more information about the disinfection
operation.
T
D
E
F
G
Field settings
Notes :
1. Reheat temperature should have lower value than storage temperature.
2. If storage temperature is higher than the disinfection temperature and if this value is high
Note :
More details about setback function can be found in setting [2].
Test Operation
Second
code
Setting name
Automatic setback and disinfection set point
00
Set point: disinfection operation temperature
01
Disinfection operation time duration
02
Leaving water setback temperature
03
Room setback temperature
[5-00] Set point: disinfection water temperature to be reached.
[5-01] Interval: time period defining how long the disinfection temperature set point should
be maintained.
A
B
A
Storage operation (if activated)
B
Reheat operation (if activated)
C
Disinfection operation (if activated)
D
Disinfection operation temperature [5-00] (e.g. 70°C)
E
Hot water storage temperature [b-03] (e.g. 60°C)
F
Reheat maximum water temperature [b-01] (e.g. 45°C)
G
Reheat minimum water temperature [b-00] (e.g. 35°C)
t
Time
T
Domestic hot water tank temperature
enough according national and local regulations, you can disable the disinfection function.
[5-02] Leaving water setback temperature.
[5-03] Room setback temperature.
C
t
Field Setting
Default
value
Range
Step
70
60~75
5
10
5~60
5
5
0~10
1
18
17~23
1
Unit
°C
min
°C
°C
93