ESIE09-08
[9] Automatic temperature compensation
First
code
9
If needed, it is possible to adjust some thermistor value of the unit by a correction value. This
can be used as countermeasure for thermistor tolerances or capacity shortage.
The compensated temperature (= measured temperature plus compensation value) is then
used for controlling the system and will be displayed in the temperature read-out mode.
Test Operation
Second
code
Setting name
Automatic temperature compensation
00
Leaving water temperature compensation
value
01
Domestic hot water tank compensation value
02
Thermo ON/OFF admission
[9-00] Leaving water temperature compensation value
[9-01] Domestic hot water tank compensation value
[9-02] Thermo ON/OFF admission
By changing this value the operation range for space heating operation can be modified.
If the ambient temperature becomes higher than (24°C + the value of [9-02]) no space
heating is possible.
Space heating can be requested as long as the ambient temperature is lower than (20°C +
the value of [9-02]).
Example: [9-02] = –2°C
T
A
C
C
B
A
No space heating operation possible
B
Request for space heating possible
C
Hysteresis area
T
Ambient temperature
Default
value
0
0
0
24°C–2°C = 22°C
20°C–2°C = 18°C
Field Setting
Range
Step
Unit
–5~5
0.5
°C
–5~5
0.5
°C
–5~5
0.5
°C