8

Boiler installation

This section details how to install your boiler correctly.
These details include:

– Flue gas connection

– Water connections
– Electrical connection
– Burner installation (if not fitted at the factory)
– Fuel connection
8.1
Flue gas connection
In different countries, different requirements apply to the
flue gas connection.
Create the flue gas connection in accordance with
the requirements applicable in your country.

8.1.1 Fitting the flue pipe sealing collar

We recommend that a flue pipe sealing collar
(accessory) is used to ensure the best seal.
Push the jubilee clips over the flue pipe.
Push the flue pipe as far as possible onto the flue
outlet.
Place the flue pipe sealing collar around the flue
pipe–flue outlet joint so that it overlaps on top.
Pull a jubilee clip onto the flue outlet and a second
clip onto the flue pipe.
Tighten the jubilee clips so that the flue pipe sealing
collar fits smooth and snug.

8.1.2 Fitting the flue gas temperature sensor (accessory)

Weld the connector into the flue pipe at a distance of
2 × flue pipe diameter (2 × Ø A) from the flue outlet.
Fit the flue gas temperature sensor (
temperature sensor documentation).
Logano G215 WS - We reserve the right to make any changes due to technical modifications.
Fig. 50 Installing the flue pipe sealing collar (schematic)
1 Flue pipe
2 flue pipe sealing collar
3 Boiler flue outlet
4 Jubilee clips
flue gas
Fig. 51 Fitting the flue gas temperature sensor (schematic)
1 Coupling
2 Flue gas temperature sensor
Boiler installation
3
2
1
2
1
8
4
35

Hide quick links: