3.3.4 Fuel conditions

Operating conditions
Permissible fuels for boilers
without integral burners
Contamination
Biogases,
Sewer gas,
Pit gas,
Methane
Tab. 5
Fuels

3.3.5 Mains power supply conditions

Operating conditions
Mains power supply voltage
Fuse
Frequency
Protection
Tab. 6
Mains power supply
Logano G215 WS - We reserve the right to make any changes due to technical modifications.
Notes – detailed requirements
This boiler can be operated with the following fuels. Select a burner which is
suitable for one of these fuel types:
– Fuel oil in accordance with the burner specification
Reduce the maintenance/cleaning intervals, if fuel oil of a lesser quality
(kinematic viscosity > 6 mm
maintenance and cleaning procedures at least twice annually.
– Natural gas in accordance with the burner specification
– LPG in accordance with the burner specification
– Biogas, sewer gas, methane, waste ground gas in accordance with the
following operating conditions
Technically free of contaminants (for example dust, water vapour, liquid), i.e.
constant operation will not lead to the accumulation of contaminants causing a
reduction in the cross-section of valves, strainers and filters.
The following operating conditions must be met:
– Constant boiler water temperature, min. 75 °C
– Uninterrupted operation
– Minimum return temperature above the dewpoint – in this case at least
60 °C, i. e. raising the return temperature
– Regular cleaning and maintenance, possibly chemical cleaning with
subsequent preservation
Notes – detailed requirements
185 – 244 V
Observe the voltage range of the burner and control devices used. The
housing/boiler must be earthed for functional and personal protection reasons.
10 A
47,5 – 52,5
Sinusoidal voltage curve
Hz
IP40 (protection against touch and the ingress of foreign bodies> 1 mm Ø, not
water protection)
Specifications