An alternate method of wiring the XP-8600 power supply is to use a single set of wires
(+ and -) from the DC source, and then tie the XP-8600's wiring lugs together: + to + and
- to -. See
Figure
Enterasys Xpedition 8000/8600 Getting Started Guide
6 Gauge Wire
From - 48 Volt
source
6 Gauge Wire
From + 48 Volt
Source
Figure 29. Splitting each source wire to two 12 gauge wires
30.
To True
Ground
Figure 30. Tying XP-8600 DC supply lugs together
Conductive
Splitter Block
12 Gauge Wire
12 Gauge Wire
Conductive
Splitter Block
12 Gauge Wire
12 Gauge Wire
Both positive (+) and both
negative (-) lugs are tied
together
From Power
From Power
Source
Source +
Installing the Hardware
RS 8600
Wiring Lugs
-
-
+
+
57