VIPER 2 FLAVOR, VIPER 3 FLAVOR & VIPER 4 FLAVOR Service Manual Release Date: October 28, 2008 Publication Number: 621260373SER Revision Date: May 14, 2012 Revision: H Visit the IMI Cornelius web site at www.cornelius.com for all your Literature needs.
Commercial Warranty. Cornelius will not be responsible for any repair, replacement or other service required by or loss or damage resulting from any of the following occurrences, including but not limited to, (1) other than normal and proper use and normal...
FCB equipment. Cornelius equipment service manuals contain instructions on how to program settings within the control system. Operators who have not been trained on servicing Cornelius FCB equip- ment should not attempt to modify equipment settings but should contact an accred- ited service provider.
Cornelius recommends that the viscosity settings be set at the lowest possible set- ting to achieve the desired drink quality. In most typical installations using a sugar- based syrup, acceptable drink quality can be achieved by programmed viscosity set- tings in the range of 3-5 for Viper.
Action Reverse the procedure to install the new compressor. Replace the dryer. Evacuate the system and recharge it according to the Cornelius nameplate on the unit. Replace the side panels and rear cover. Reconnect power to the unit and test the unit.