S ystem Trou bl e M es s ages
The following list shows the systems trouble messages
including a description of what has caused the trouble event to
occur. System Trouble events are also recorded in the System
Event Log.
Power Missing
This trouble message will display when the AC mains power supply to
the panel is disconnected or failled and will clear when the power is
reconnected. The Mains Power Icon in the keypad will also flash when
the power is missing.
Battery Low
This trouble message will display if the panel's backup battery voltage
has dropped below 11.5 volts DC during a battery test and will clear
when the voltage is above 12.5 volts during a subsequent battery test.
Battery Missing
This trouble message will display if the panel detects that the system's
backup battery is missing or has been disconnected.
Battery Reversed
This trouble message will display if the panel detects that the battery
connection leads are reversed.
Voltage Low
TBA
Voltage High
TBA
RF Rxer Missing
This trouble message will display if the panel detects the RF receiver
is missing or disconnected. The trouble will clear when the receiver is
reconnected.
RF Rxer Tamper
This trouble message will display if the panel detects that the tamper
circuit on the RF receiver is faulted.
RF Rxer Jammed
This trouble message will display if the connected RF receiver detects
RF noise levels that may prevent it from working correctly.
RF Signal Low
This trouble message will display when a connected RF peripheral
device such as a RF PIR sends a low battery signal to the receiver.
Comms Trouble R1
This trouble message will display if the panel has failed to send
pending reports to Report Destination 1. All possible call attempts will
be made before the trouble message is displayed.
Comms Trouble R2
This trouble message will display if the panel has failed to send
pending reports to Report Destination 2. All possible call attempts will
be made before the trouble message is displayed.
Comms Test Fail
This trouble message will display if the panel has failed to send a
periodic test report signal to the base station.
11-2
Buss Trouble
This trouble message will display if the panel failed to communicate
to a system device which is connected to the LAN bus (e.g. keypad
etc).
Default PIN Trbl
This trouble message will display if the panel detects that either the
Installer PIN or User 1 PIN is still set to the factory default PIN. Change
the PIN to clear the fault.

Date And Time

This trouble message will display if the system date and time has not
been set. Program the correct date and time to clear the fault.
Enclosure Tamper
This trouble message will display if the panel detects that it's
enclosure tamper input is unsealled. Close the tamper switch to clear
the fault.
Panel Missing
This trouble message will display if the system detects that another
panel on the same system has been disconnected. This message is
only relevant when using the Solution-128 panel.
Siren Trouble
This trouble message will display if the panel detects that the horn
speaker has been disconnected from the output terminal or is open
circuit. Horn speakers can be connected to Output 1 and or Output 2
and must be programmed as horn speaker outputs.
Telco Line Trouble
This trouble message will display if the panel detects that the
telephone line has failed or been disconnected for a minimum of 30
seconds. The trouble will clear once the line has been restored for at
least 1 minute.
LAN Overload
This trouble message will display if the panel detects that the current
load on the LAN+ power terminal has exceeded it's maximum rating
See MENU 7-3-2 — Fuse Options.
of 1Amp DC.
Comm+ Overload
This trouble message will display if the panel detects that the current
load on the COMM+ terminal has exceeded it's maximum rating of
See MENU 7-3-2 — Fuse Options.
3Amp DC.
Accessory Overld
This trouble message will display if the panel detects that the
current load on the +12V accessory power terminal has exceeded it's
maximum current rating of 1Amp D.C.
Options.

Call For Service

This trouble message will display when the Service Interval Timer
expires. To clear the message the installer must enter and exit
programming mode. See MENU 2-9-2 — Service Interval.
Time For Service
This trouble message will display when the User Test Interval timer
expires. To clear the message the user must enter and exit walk test
mode. See MENU 2-9-1 — User Test Interval.
Memory Fault
This occurs if the memory checksum is corrupted. To try and correct
this, enter programming mode and make a programming change like
a user name then exit programming mode. If this problem still persists
you must do a full system default.
See MENU 7-3-2 — Fuse