6.35.2 Setting of optional meter outputs
~ , ~ : Meter output settings
For details, refer to Instruction Manual (E6581341) specified in Section 6.42.
6.35.3 Calibration of analog outputs
: FM voltage/current output switching
, : FM output gradient characteristic and bias adjustment
, : AM output gradient characteristic and bias adjustment
Function
Output signals from FM/AM terminals are analog voltage signals. Their standard setting range is from 0 to
10Vdc.
The output current from terminal FM can be changed to 0 to 20mAdc (or 4 to 20mAdc) by changing the settings
of terminal SW2 and a parameter.
[Parameter setting]
Title
6
Note: To switch to 0-20mAdc (4-20mAdc), set to .
FM terminals setting example
SW2: 0-10V/0-20mA side
, = = (%)
The analog output inclination can be adjusted using the parameter
For code data 50 to 64, negative inclination is invalid.
Function
FM voltage/current output
switching
FM output gradient
characteristic
FM bias adjustment
AM output gradient
characteristic
AM bias adjustment
(mA)
20
0
0
100%
Internal calculated value
SW2: 0-10V/0-20mA side
= = = (%)
(mA)
20
: Large gain
0
0
100%
Internal calculated value
Adjustment range
: Voltage 0~10V output
: Current 0~20mA output
: Negative gradient
(descending)
: Positive gradient
(ascending)
- ~ . %
: Negative gradient
(descending)
: Positive gradient
(ascending)
- ~ . %
SW2: 0-10V/0-20mA side
, = = (%)
(mA)
SW2: 0-10V/0-20mA side
= = =(%)
(mA)
F-72
E6581442
Default setting
20
4
0
100%
Internal calculated value
20
:Small gain
4
0
100%
Internal calculated value