<Basic operating>
Step
1
Set the pattern operation selection
parameter at "Enabled."
2
Set all necessary operation frequencies.
In addition, set frequencies for preset
speed operation.
3
Set the required operation time at each of
the set operation frequencies. Using
, select the unit of time to be set
(second or minute).
4
Set the sequence of each speed.
This sequence following three methods.
(1) Select a run/stop operation from the
pattern operation mode.
(2) Select a pattern group, and then set
the sequence of each speed.
6
(3) According to the required parameter
group, select pattern operation
selection 1 or 2 from input terminal
function selection to .
Selecting pattern operation
continuation signals makes it possible
to select a start/stop method.
5
Monitor displayed during pattern operation
Specify the pattern operation monitor item ( to ) that you want to display as a status monitor item
( to ). This setting makes the inverter display the pattern operating status.
Pattern and pattern group
Pattern group – remaining
number of repetitions
Operation preset speed
Remaining time of the current
pattern operation
Setting
= (Disabled)
~
~ (Preset speed operation frequencies 8~15)
~ (Preset speed operation frequency 1~15
~ (Operating time at each speed)
= (Patterned operation canceled during stop)
~=, (Pattern operation selection 1)
Condition
Marking
(A) (B)
F-56
Parameter
(Pattern operation enabled, setting in seconds)
(Pattern operation enabled, setting in minutes)
(Preset speed operation frequencies 1~7)
(Preset speed operation mode selection)
operation mode)
* Pattern operation is reset by stop/switching
operation before operating restarts.
= (Patterned operation continued during stop)
* Pattern operation is started by stop/switching
operation. The system stops temporarily on
completion of every routine, then proceeds to the
next routine.
(Number of repetitions of pattern group 1)
~ (Pattern group 1 selection 1~8)
(Number of repetitions of pattern group 2)
~ (Pattern group 2 selection 1~8)
=, (Pattern operation selection 2)
=, (Pattern operation continuation
signal)
=, (Pattern operation trigger signal)
Specification
(A): Number of the pattern group
(B): Number of the pattern
Indicates that pattern operation has been
performed 123 times.
Frequency reference with preset speed 1 data.
Current pattern is finished in 1234 sec.
Operation time is set for infinity or the system is
waiting for the next step command.