Emergency Stop - Toshiba Tosvert VF-AS1 Instruction Manual

The new high-performance inverter
Hide thumbs Also See for Tosvert VF-AS1:
Table of Contents

Advertisement

Be sure to select this setting if the main power supply is turned on and off endlessly for reasons of sequence, as
shown below, in the event the control power supply backup device fails or not connected.
Control power supply
backup device (option)
<Example of a situation in which the main power supply is turned on and off endlessly>
In the example of connection shown above, if the control power supply backup device (optional) fails or not
connected and becomes incapable of supplying control power, control power is supplied from the inverter's main
circuit and operation is continued without interruption. If the inverter is tripped under these circumstances because of
a ground fault or overcurrent :
(1) The FL relay is triggered and the main power supply is shut off by the MC.
(2) As a result of shutoff by the MC, the voltage in the inverter's main circuit and control circuit drop.
(3) As a result of a drop in control voltage, the FL relay recovers from a trip.
(4) The release of the FL relay turns the MC back on.
(5) Operation is restarted and if the problem causing the inverter to be tripped is not eliminated, the inverter is tripped
again, the situation in (1) arises again, and thus the above cycle of operation is repeated endlessly.

6.33.3 Emergency stop

 : Emergency stop
 : Emergency DC braking control time
• Function
Emergency stop mode can be selected. At emergency stop, a trip message ("") is displayed. FL relay can
be deactivated using the output function selection.
1) Emergency stop by terminal operation
Emergency stop can be performed with the a or b-contact. Assign the emergency stop function to a terminal as
described below, and select a stop mode.
Input terminal
2) Emergency stop
=: The motor is brought to a stop within the time specified with 
=: DC braking is performed at the current specified with  (DC braking current) for the time
specified with  (emergency DC braking control time).
=: The motor is brought to a stop within the time specified with  (deceleration time 4).
In case of
3
- 200~240V
-50/60Hz
a-contact
CC
Use this setting to bring the motor to a stop within time different from the normal
deceleration time specified with .
F-59
MC
R/L1
S/L2
T/L3
+SU
CC
FLA
RUN
MC
FLB
FLC
RUN
Input terminal
CC
E6581442
6
b-contact