Selection Of Operation Mode - Toshiba Tosvert VF-AS1 Instruction Manual

The new high-performance inverter
Hide thumbs Also See for Tosvert VF-AS1:
Table of Contents

Advertisement

Frequency setting with operation panel and operation with terminal board (=)
This setting is used to set the frequency using the operation panel and to perform operation control using the terminal
board.
Use the
and
In sink logic mode: PWR-P24/PLC ON: Standby (ON (short-circuited) by default),
F-CC ON: Forward run, R-CC ON: Reverse run.
Frequency setting and operation with operation panel (=)
This setting is used to set the frequency and to perform operation control, using the operation panel.
Use the
and
Use the
and
RUN
5.5

Selection of operation mode

  : Command mode selection
  : Frequency setting mode selection 1
• Function
5
These parameters are to program which command to the inverter (from operation panel, terminal board, remote
input device or options) will be given priority in running/stopping the operation and in frequency setting (speed).
<Command mode selection>
[Parameter setting]
Title

[Programmed value]
:
Terminal board operation
:
Operation panel operation
:
2-wire RS485 communication operation
:
4-wire RS485 communication operation
:
Communication option input enabled
* There are two types of function: the function that conforms to commands selected by , and the function that
conforms only to commands from the terminal board.
 Refer to the table of input terminal function selection in Section 7.2.
* When priority is given to commands from a linked computer or terminal board, they have priority over the setting of
.
keys to set the frequency.
keys to set the frequency.
keys to perform operation control.
STOP
Function
:Terminal input enabled
:Operation panel input enabled (including LED/LCD option
Command mode
input)
:2-wire RS485 communication input
selection
:4-wire RS485 communication input
:Communication option input
ON and OFF of an external signal Runs and stops operation.
Press the
a run. (including LED/LCD option input)
Adjustment range
RUN
STOP
and
keys on the operation panel to Run and stop
Run and stop commands are entered from the
2-wire RS485 communications device.
(Communication No.: FA00)
Run and stop commands are entered from the 4-wire
RS485 communications device.
(Communication No.: FA04)
Signals from an optional communication device are used to
start and stop operation.
 For details, refer to Instruction Manual (E6581281,
E6581343, E6581477) specified in Section 6.42.