Omron OS32C Series User Manual page 69

Safety laser scanner
Hide thumbs Also See for OS32C Series:
Table of Contents

Advertisement

3.
New configuration screen is displayed.
Fig. 3-18 New Configuration Parameters
• Safety Critical Parameters
1. External Device Monitoring (EDM) : When enabled the OS32C can monitor the N.C. contacts of the
2. Response Time
3. Monitoring Zone
4. Zone Delay
5. Operating Mode
6. Minimum Object Resolution
Basic Operation of Configuration Software
external control relays. These relays are controlled by the
OSSD safety outputs.
: Configures a time period for OS32C safety output from ON to
OFF. The available range is from 80ms to 680ms in increments
of 40ms.
: To configure only one zone set, select Single zone. To
configure more than one zone, select Multiple zone.
: Select the desired Zone Delay. The available range is 20ms to
320ms in increments of 20ms.
: A user can select from Automatic Start, Start Interlock, or
Start/Restart Interlock.
: Select the minimum object size to be detected by the scanner.
Select from 30mm, 40mm, 50mm, and 70mm.
The minimum object resolution is displayed on the seven
segment display for 5 seconds on power up. Refer to "Status/
Diagnostic Display" in Chapter 2 for more detail.