Output Mode
Disabled
Safety Output Information Mode
Lockout Information Mode
Warning Zone 1 Information Mode
Warning Zone 2 Information Mode
Window Contamination Warning Mode
*1. When the polarity is Active ON, the output modes will be active when the outputs are ON.
*2. When the polarity is Active OFF, the output modes will be active when the outputs are OFF.
NOTE: If the unit enters a fault state, all outputs will be OFF, except in Lockout Information Mode.
Table2-8 Output Polarity
Active ON *1
Output always OFF
Same as OSSDs (output ON when safety
zone is clear)
Output ON when fault occurs
Output ON when zone 1 infringed
Output ON when zone 2 infringed
Output ON when window contaminated
Operating States & Output Modes
Active OFF *2
Output always OFF
Opposite of OSSDs (output OFF when
safety zone is clear)
Output OFF when fault occurs
Output OFF when zone 1 infringed
Output OFF when zone 2 infringed
Output OFF when window contamined