Honeywell ADEMCO MX8000 Installation And Operation Manual page 93

Digital alarm receiver
Hide thumbs Also See for ADEMCO MX8000:
Table of Contents

Advertisement

Select
Line
Device
Device
Type
Menu
Choice
MX8000–
LC1
Edit Line
Line #
1 Line
(cont'd)
(cont'd)
(cont'd)
Table 5–11: Line Device Menu Options (cont'd)
Choice
Choice
Misc. Line
Call Hang-
Options
up
(cont'd)
BFSK Auto
3/1 Restore
4/2 Out
FBI
Ademco
Auto Opt
Pulse
Extended
Extended
Output
Choice
Default
60-180 sec
120 sec
4/2
High Speed
3/1
High Speed
Normal
High Speed
S/Fast
LAR300
Extended
Not Extended
High Speed
4/2
Section 5 – Programming
Comments
Sets the maximum
amount of time that a
call can last before the
receiver hangs up on
the call if an event is
not in progress. See
page 5–66 for details.
In High Speed,
messages with event
codes of B, C, E, and
F are translated to
ADEMCO High Speed
messages.
Standard method:
123 2, 123 9
Converted to High
Speed:
0123 5355 5555 7
In High Speed mode,
messages with event
codes of B and C are
translated to High
Speed Opening and
Closing messages,
respectively.
A sequence of 1234 B
, BBBB 7 is combined
into a 4-2 message of
1234 B7. (Applies to
B,C,E,F). This mes-
sage would either be
put out to Automation
as 4-2 or High Speed.
When the option is
selected, the receiver
does not combine the
expanded messages.
They are output in the
same form as
received.
If low speed expanded
messages are
received and
combined (See Pulse
Extended above), the
messages are output
to Automation as 4-2
format messages. For
example, a sequence
of 1234 B , BBBB 7 is
combined and output
as a 4-2 message of
1234 B7.
5–37

Advertisement

Table of Contents
loading