8.4.7.2
Force Hang-up Request
This command is used to immediately hang up the phone line regardless of the state of the line card.
To Force Hang-up:
<$05><Receiver ID><$22><LC#><V-byte><$0D>
8.4.7.3
Add or Delete a Listen-in Account
If the account number of a control panel is in the listen-in account list, when that control panel calls in to the
receiver, the receiver will perform a listen-in operation with that control panel. The maximum length of a
listen-in account number is 8 characters and may include wild card characters (# and or *). Each line card
can have up to 20 listen-in account strings. See also Section 5.5.2.4.
Note: The listen-in account list applies to panels that do not send listen-in commands as a part of their
message (Contact ID E606 or SIA LF and LE).
To Add a Listen-in Account:
<$04><Receiver ID><$22><LC#><$22><Act#><V-byte><$0D>
Component
<$04>
<Receiver ID>
<$22>
<LC#>
<$22>
<Act#>
<V-byte>
<$0D>
To Delete a Listen-in Account:
<$03><Receiver ID><$22><LC#><$22><Act#><V-byte><$0D>
Component
<$03>
<Receiver ID>
<$22>
<LC#>
<$22>
<Act#>
<V-byte>
<$0D>
Table 8–16: Log-off Request Components
Component
<$4B>
Command request identifier. See Table 8–14.
<Receiver ID>
Receiver ID number. 1 or 2 ASCII digits.
<$22>
Separator
<User PIN>
The user's PIN code.
<V-byte>
Validation Byte (V-byte). See 8.4.5.
<$0D>
End of message indicator.
Table 8–17: Force Hang-Up Request Components
Component
<$05>
Command request identifier. See Table 8–14.
<Receiver ID>
Receiver ID number. 1 or 2 ASCII digits.
<$22>
Separator
<LC#>
The LinePort number.
<V-byte>
Validation Byte (V-byte). See 8.4.5.
<$0D>
End of message indicator.
Table 8–18: Add Listen-in Account Request Components
Command request identifier. See Table 8–14.
Receiver ID number. 1 or 2 ASCII digits.
Separator
The LinePort number.
Separator
Account number to be added to the listen-in account list.
Validation Byte (V-byte). See 8.4.5.
End of message indicator.
Table 8–19: Delete a Listen-in Account Request Components
Command request identifier. See Table 8–14.
Receiver ID number. 1 or 2 ASCII digits.
Separator
The LinePort number.
Separator
Account number to be deleted from the listen-in account list.
Validation Byte (V-byte). See 8.4.5.
End of message indicator.