Figure A-2 Typical Setup For Setting Range Values Using Local Zero And Span Adjustments - Honeywell ST 3000 Installation Manual

Smart transmitter
Hide thumbs Also See for ST 3000:
Table of Contents

Advertisement

A.4
Setting Range Values (Local Zero and Span),
Procedure, continued
Figure A-2
Typical Setup for Setting Range Values Using Local Zero and Span Adjustments.
+
Power
Supply
-
Receiver
250 ohm
58
Table A-3
Setting Range Values Using Local Zero and Span
Adjustments, Continued
Step
Wait 30 seconds so that changes have been copied to the
10
transmitter's non-volatile memory.
11
Remove applied pressure and turn OFF transmitter power.
12
Replace end-cap on PWA side of electronics housing and tighten
lock.
Remove milliammeter from TEST terminals and replace end-cap and
13
tighten lock.
Turn ON transmitter power and check smart meter reading, if
14
applicable.
+
-
Field
Terminals
VAR
SEL.
SPAN
Smart Meter with
ZERO
Local Zero and Span
installed on PWA side
of electronics housing
ST 3000 Release 300 Installation Guide
Action
ST 3000
UPPER
VALUE
%
0
100
0
0
0
UNITS
SET
AN ALOG
In H O
2
LOWER
VALUE
Continued
Milliammeter
2/05