Table 4. User Settings (continued)
Description
Battery Setup
Power Strategy
Start Screen
User Password
Audible Alarms
Unsynchronized Transfer to Bypass
Transfer to Bypass When Overload
Automatic Start Delay
Control Commands from X-Slot1
Control Commands from X-Slot2/Serv
X-Slot Signal Input Activation Delay
Site Wiring Fault Notice
Reset Custom Event Settings
REPO Configuration

Operating Modes

Available Settings
Number of EBMs: [0 through 4]
(See "Configuring the UPS for EBMs" on page 74.)
Battery Low Alarm Level: [1.750 through 1.950 volts per cell]
(See "Setting the Battery Low Alarm Level" on page 75.)
Automatic Battery Tests: [Enabled] [Disabled]
(See "Running Automatic Battery Tests" on page 75.)
External Battery Capacity: Set Watts per cell
Use this setting only in conjunction with customer-supplied
external batteries and the External Battery Interconnect.
[High Efficiency] [Standard]
For more information, see the following section, "Operating
Modes."
Eaton logo
Mimic screen (see Figure 45 on page 63)
[Enabled] [Disabled]
If Enabled is selected, the password is USER.
[Normal Sound] [Disabled]
[Allowed] [Not Allowed]
[After a delay] [Immediately]
-1 through 32767 seconds
(-1 means disabled)
[Allowed] [Disabled]
Selecting Disabled prevents load commands such as Load Off
through the X-Slot, including remotely.
0 through 65 seconds
[Enabled] [Disabled]
0 through 32
[Enabled][Disabled]
The BladeUPS module front panel indicates the UPS status through the UPS
indicators. Figure 44 on page 63 shows the UPS front panel indicators and controls.

Normal Mode

During Normal mode, the
UPS. The UPS monitors and charges the batteries as needed and provides filtered
power protection to your equipment.
By default, the BladeUPS module operates on a High Efficiency setting that minimizes
heat contribution to the rack environment. The system bypass input directly supplies
the system output with three-phase AC power, and the UPS stands ready to
automatically transfer to double-conversion (Standard) operation as needed. The
battery recharges when necessary.
EATON BladeUPS
®
(12 kVA) User's Guide
Default Setting
0
(means internal batteries only)
1.880 V/cell
(provides approximately 2.5 min warning
for the UPS)
Enabled
(automatically runs the battery test once
a month)
None
High Efficiency
Eaton logo
Disabled
Normal Sound
Not Allowed
After a delay
0s
Allowed
5s
Enabled
Total: 0/32
Enabled
indicator illuminates solid and the utility powers the
S
164201649 Rev 4www.eaton.com/powerquality
OPERATION
67