6.
Check each UPS front panel display for active alarms or notices (other than
"Batteries Disconnected"). Resolve any active alarms before continuing.
See "Troubleshooting" on page 105.
7.
Switch all UPS battery circuit breakers to the ON (
8.
If optional EBMs are installed, switch all EBM battery circuit breakers to the

ON (
) position.
9.
Verify that the "Batteries Disconnected" alarm on each UPS has cleared. Verify
that no other alarms appear on any UPS front panel display.
If an
indicator is flashing on any UPS, do not proceed until all alarms are clear.
Check the UPS status from the front panel to view the active alarms. Correct the
alarms and restart if necessary.
10. On any UPS, press any button on the front panel display to activate the menu
options, and then press the button until the TURN UPS ON/OFF menu displays.
11. Press the
button to display the TURN SYSTEM ON option; press the
button.
12. Confirm the selection. Press and hold the
UPS stops beeping.
Verify that the
indicator illuminates solid on each UPS, indicating that the
UPS is operating normally and any loads not connected through the load
connector are now energized.
If the
indicator on any UPS is flashing, do not proceed until all alarms are
clear. Check the UPS status from the front panel to view the active alarms.
Correct the alarms and restart if necessary.
NOTE For a parallel-ready system (a single UPS installed to be part of a future parallel system), set the
Parallel Operation Settings / Parallel Operation Mode to "Capacity Mode" to prevent unnecessary alarms (see
Chapter 4, "Operation").
Each UPS should be in Normal mode. By default, Normal mode operates on the
High Efficiency setting (see "Normal Mode" on page 67).
13. To energize loads connected through the load connectors, switch all load
connector circuit breakers to the ON (
14. On any UPS, press the
EATON BladeUPS
®
(12 kVA) User's Guide
button for three seconds, until the

) position.
ESC
button until the Start screen appears.
S
164201649 Rev 4www.eaton.com/powerquality