Eaton Powerware Series User Manual page 55

Bladeups 12 kva powerware series
Hide thumbs Also See for Powerware Series:
Table of Contents

Advertisement

Standalone/
Parallel
(remove)
For Parallel
Use Only
Redundant Signal Cable
Standalone/
Parallel
For Parallel
Use Only
Standalone/
Parallel
Figure 36. Typical CAN Bridge Card and Redundant Signal Wiring
12. Install a redundant signal cable between the For Parallel Use Only and
Standalone/Parallel terminals on each UPS as shown in Figure 36.
Be sure to check correct polarity when installing the cable.
If polarity or wiring is not correct, the parallel system does not operate normally. For example, when shutting
down one UPS, the remaining UPS transfers the load to bypass instead of supporting the load. Verify that all
wiring is correct for proper operation.
13. Remove the Standalone/Parallel terminal block connector from the last UPS
(UPS 3 in Figure 36).
EATON BladeUPS
®
(12 kVA) User's Guide
Blue Terminating Plug
C A U T I O N
S
164201649 Rev 4www.eaton.com/powerquality
INSTALLATION
UPS 3
CAN
CAN
IN
OUT
Blue Terminating Plug
UPS 2
CAN Bridge Card Cable
UPS 1
47

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Bladeups 12Bladeups 12i

Table of Contents