Remove the six screws on the conduit landing plate and retain. Remove the plate
and retain. See Figure 7.
Bottom Entry Rack
Figure 7. Removing the Conduit Landing Plate
4.
Use a Greenlee
punch to provide one or more holes in the conduit landing plate
®
to accommodate the input and output wiring from the utility to the
BladeUPS Bar.
Replace the conduit landing plate.
5.
Connect the input, output, and ground wires to the BladeUPS Bar terminal block
according to Figure 8 and Table 2. Route the three input phases and the input
neutral through the mounted or loosened ferrite assembly (see Figure 6).
Ground
Top Entry
Terminal Block
EATON BladeUPS
®
(12 kVA) User's Guide
Ground
Figure 8. BladeUPS Bar Terminal Block
S
164201649 Rev 4www.eaton.com/powerquality
INSTALLATION
Top Entry Rack
Bottom Entry
Terminal Block
23