Eaton Powerware Series User Manual page 108

Bladeups 12 kva powerware series
Hide thumbs Also See for Powerware Series:
Table of Contents

Advertisement

SPECIFICATIONS
Table 11. BladeUPS Bar 60
Dimensions (WxDxH)
Weight
UPS Connections
Rack Placement
Table 12. BladeUPS Module Rack
Dimensions (WxDxH)
Weight
Table 13. Electrical Input
Nominal Voltage
Nominal Frequency
Frequency Range
Default Frequency
Rated Input Current
Connections
Noise Filtering
Input Power Factor
Input Mode
100
EATON BladeUPS
BladeUPS Bar: 19 kg (42 lb); Wireway enclosure: 20 kg (45 lb)
Bottom wireway fits into the bottom 6U of standard rack space.
Top wireway fits into the top 6U of standard rack space.
Side panels (each): 8.5 kg (19 lb); Casters (4): 5 kg (10 lb)
BladeUPS 12 Module
120/208V three-phase
50/60 Hz
45–65 Hz
Auto-detected
IEC 309-60A power cord
For paralleling, a single Anderson input/output cord connects to the
S
®
(12 kVA) User's Guide
164201649 Rev 4www.eaton.com/powerquality
140 x 161 x 1838 mm (6.3" x 4.4" x 72.4")
Total weight: 39 kg (87 lb)
Up to 6, using Anderson input/output connectors
610 x 1067 x 2032 mm (24" x 42" x 80")
Rack without side panels or casters: 99 kg (219 lb);
Total weight: 121 kg (267 lb)
36A
BladeUPS Bar (see Table 9 on page 99).
MOVs and common mode line filter
High Efficiency setting: load dependent
Standard setting: >0.99
Three-phase
BladeUPS 12i Module
230/400V three-phase
50/60 Hz
45–65 Hz
Auto-detected
24A
IEC 309-32A power cord

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Bladeups 12Bladeups 12i

Table of Contents