2 Instructions

SCL2

Instruction
SCALING 2
Symbol
Applicable Program Areas
Area
Usage
Operands
Operand
S
Source word
P1
First parameter word
R
Result word
P1: First Parameter Word
15
P1
15
P1+1
15
P1+2
Operand Specifications
Word addresses
Area
CIO
WR
HR
S, P1, R
OK
OK
OK
2-280
Mnemonic
Variations
SCL2
@SCL2
Step program areas
OK
Description
0
Offset of linear function
8000 to 7FFF (signed binary)
0
8000 to 7FFF (signed binary)
0
0000 to 9999 (BCD)
AR
T
C
DM
OK
OK
OK
OK
Function
code
Converts signed binary data into signed BCD data
486
according to the specified linear function. An offset
can be input in defining the linear function.
SCL2
SCL2(486)
S: Source word
S
P1: First parameter word
P1
R
R: Result word
Subroutines
OK
Data type
INT
WORD
WORD
Note P1 to P1+2 must be in the same area.
Indirect DM addresses
Constants
@DM
*DM
OK
OK
---
CP1E CPU Unit Instructions Reference Manual(W483)
Function
Interrupt tasks
OK
Size
1
3
1
CF
Pulse bits
TR bits
---
---
---