Omron SYSMAC CP Series Instruction & Reference Manual page 357

Cpu unit
Hide thumbs Also See for SYSMAC CP Series:
Table of Contents

Advertisement

Operation
Purpose
Application
Stopping
Stop pulse
Immediate stop
pulse output
output
Stop pulse
Immediate stop
output
Independent Mode Positioning
When independent mode operation is started, pulse output will be continued until the specified number
of pulses has been output.
Note
• Pulse output will stop immediately if the CPU Unit is changed to PROGRAM mode.
• The number of output pulses must be set each time output is restarted.
• The number of output pulses must be set in advance with PULS(881). Pulses will not be output for
SPED(885) if PULS(881) is not executed first.
• The direction set in the SPED(885) operand will be ignored if the number of pulses is set with PULS(881)
as an absolute value.
Operation
Purpose
Application
Starting
To output with
Positioning
pulse output
specified
without accel-
speed
eration or
deceleration
Changing
To change
Changing the
settings
speed in one
speed in one
step
step during
operation
CP1E CPU Unit Instructions Reference Manual(W483)
Frequency changes
Pulse frequency
Present frequency
Execution of INI(880)
Pulse frequency
Present frequency
Execution of SPED(885)
Frequency changes
Specified number of
Pulse frequency
pulses (Specified with
PULS(886).)
Target
frequency
Execution of
Outputs the specified
SPED(885)
number of pulses
and then stops.
Specified number
of pulses
Pulse
(Specified with
frequency
PULS(886).)
New target
frequency
Original target
frequency
Execution of SPED(885)
(independent mode)
SPED(885) (independent
mode) executed again to
change the target
frequency. (The target
position is not changed.)
Description
Stops the pulse output
immediately.
Time
Stops the pulse output
immediately.
Time
Description
Starts outputting pulses
at the specified fre-
quency and stops
immediately when the
specified number of
pulses has been out-
put.
Time
Note The target posi-
tion (number of
pulses) cannot be
changed during
positioning (pulse
output).
SPED(885) can be exe-
cuted during position-
ing to change (raise or
Number of pulses
lower) the pulse output
specified with
frequency in one step.
PULS(886) does
The target position
not change.
(specified number of
pulses) is not changed.
Time
2 Instructions
Procedure/
instruction
SPED(885) (Continu-
ous)
INI(880)
SPED(885) (Continu-
ous)
SPED(885) (Continu-
2
ous, Target frequency
of 0 Hz)
Procedure/
instruction
PULS(886)
SPED(885)
(Independent)
PULS(886)
SPED(885)
(Independent)
SPED(885)
(Independent)
2-321