I/O Memory Allocation
Address
Words
Bits
A402
A40213 Interrupt
Task Error
Flag
(Non-fatal
error)
A40215 FAL Error
Flag
(Non-fatal
error)
A403
A40300
Memory
to
Error Loca-
A40308
tion
224
Name
ON when the Detect Interrupt
Task Errors setting in the PLC
Setup is set to "Detect" and an
interrupt task is executed for
more than 10 ms during I/O re-
freshing of a C200H Special I/O
Unit or a SYSMAC BUS I/O Unit.
This flag will also be turned ON if
an attempt is made to refresh a
Special I/O Unit's I/O from an
interrupt task with IORF(097)
while the Unit's I/O is being re-
freshed by cyclic I/O refresh-
ing(duplicate refreshing).
ON when a non-fatal error is
generated by executing
FAL(006). The CPU Unit will
continue operating and the
ERR/ALM indicator on the front of
the CPU Unit will flash.
The bit in A360 to A391 that cor-
responds to the FAL number
specified in FALS(006) will be
turned ON and the corresponding
error code will be written to A400.
Error codes 4101 to 42FF cor-
respond to FAL numbers 001 to
2FF (0 to 511).
(This flag will be turned OFF
when the error is cleared.)
When a memory error occurs, the
Memory Error Flag (A40115) is
turned ON and one of the fol-
lowing flags is turned ON to in-
dicate the memory area where
the error occurred
A40300: User program
A40304: PLC Setup
A40305: Registered I/O Table
A40307: Routing Table
A40308: CS/CJ-series CPU Bus
Unit Settings
When a memory error occurs, the
CPU Unit will continue operating
and the ERR/ALM indicator on
the front of the CPU Unit will
flash.
(The corresponding flag will be
turned OFF when the error is
cleared.)
CS/CJ-series PLC
Function
CX-Simulator
Settings
Function
1: Interrupt
Not used.
task error
0: No error
1:
Same as
FALS(006)
CS/CJ-series
error oc-
PLC.
curred
0:
FALS(006)
not exe-
cuted
1: Error
Same as
0: No error
CS/CJ-series
PLC.
Section 9-3
Settings

Hide quick links: