Omron WS02-SIMC1-E - V1.9 REV 02-2009 Operation Manual page 245

Table of Contents

Advertisement

I/O Memory Allocation
Address
Words
Bits
A264
All
Present
and
Cycle Time
A265
A266
All
Present
and
Cycle Time
A267
(0.01 ms
units)
A294
All
Task Num-
ber when
Program
Stopped
Name
These words contain the present
cycle time in 8-digit hexadecimal
with the leftmost 4 digits in A265
and the rightmost 4 digits in
A264.
These words contain the
0.01ms-unit present cycle time in
8-digit hexadecimal with the
leftmost 4 digits in A267 and the
rightmost 4 digits in A266.
0 to FFFFFFFF:
0 to 42,949,672.95 ms (0.01 ms
units) (CJ2-series PLCs only)
This word contains the task
number of the task that was being
executed when program execu-
tion was stopped because of a
program error.
(A298 and A299 contain the pro-
gram address where program
execution was stopped.)
CS/CJ-series PLC
Function
CX-Simulator
Settings
Function
0 to
Same as
FFFFFFFF:
CS/CJ-series
PLC.
0 to
429,496,72
9.5ms
0 to
Not used
FFFFFFFF:
0 to
42,949,672.
95 ms
(0.01 ms
units)
Normal
Same as
tasks:
CS/CJ-series
0000 to
PLC.
001F (task
0 to 31)
Interrupt
tasks:
8000 to
80FF (task
0 to 255)
Section 9-3
Settings
209

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sysmac ws02-simc1-eCx-simulator 1.9

Table of Contents