I/O Memory Allocation
Item
Instruction Error Op-
eration
Minimum Cycle Time
Watch
Enable
Cycle
Watch Cy-
Time
cle Time
Setting
Watch Cy-
cle Time
Setting
Fixed
Enable
Periph-
Fixed Ser-
eral Ser-
vicing Time
vicing
Time
Fixed Ser-
vicing Time
Power OFF Interrupt
Task
Power OFF Detection
Delay Time
204
CS/CJ-series PLC
Settings
0: Continue
This setting determines whether
1: Stop
instruction errors (instruction
processing errors (ER) and illegal
Default: 0
access errors (AER)) are treated
as non-fatal or fatal errors. When
this setting is set to 1, CPU Unit
operation will be stopped if the
ER or AER Flags is turned ON
(even when the AER Flag is
turned ON for an in direct DM/EM
BCD error).
Related Flags: A29508 (Instruc-
tion Processing Error Flag)
A29509 (Indirect DM/EM BCD
Error Flag)
A29510 (Illegal Access Error
Flag)
0001 to 7D00:
Set to 0001 to 7D00 to specify a
1 to 32,000 ms
minimum cycle time. If the cycle
(1-ms units)
time is less than this setting, it will
be extended until this time
Default: 0000
passes. Leave this setting at
(No minimum)
0000 for a variable cycle time.
0: Default
Set to 1 to enable the Watch
1: Bits 0 to 14
Cycle Time Setting in bits 0 to 14.
Leave this setting at 0 for a
Default: 0
maximum cycle time of 1 s.
001 to FA0: 10 to
This setting is valid only when bit
40,000 ms
15 of 209 is set to 1. The Cycle
(10-ms units)
Time Too Long Flag (A40108) will
be turned ON if the cycle time
Default: 001 (1 s)
exceeds this setting.
0: Default*
Set to 1 to enable the fixed pe-
1: Bits 0 to 7
ripheral servicing time in bits 0 to
7.
Default: 0
*Default: 4% of the cycle time
00 to FF:
This setting is valid only when bit
0.0 to 25.5 ms
15 of 218 is set to 1.
(0.1-ms units)
Default: 00
0: Disabled
When this setting is set to 1, the
1: Enabled
power OFF interrupt task will be
executed when power is inter-
Default: 0
rupted.
00 to 0A:
This setting determines how
0 to 10 ms (1-ms
much of a delay there will be from
units)
the detection of a power interrup-
tion (approximately 10 to
Default: 00
25 ms after the power supply
voltage drops below 85% of the
rated value) to the confirmation of
a power interruption. The de-fault
setting is 0 ms.
Function
Section 9-3
CX-Simulator
Settings
Function
Same as
CS/CJ-series
PLC.
Same as
CS/CJ-series
PLC.
Same as
CS/CJ-series
PLC.
Same as
CS/CJ-series
PLC.
Not used.
Not used.
Same as
CS/CJ-series
PLC.
Not used.