Advertisement

Communication protocols
ETHERNET(1,-1,14,1,1,3)
ETHERNET(1,-1,14,1,2,2)
Change input address to 100:
ETHERNET(1,-1,14,1,0,100)
4.3

Serial protocol

The TJ2-MC64 has a DB-9 connector that contains two serial ports:
Port 1: RS232
Port 2: RS422 or RS485, depending on the switch settings
See the Trajexia Hardware Reference manual for details.
Both ports can independently support these protocols:
Host Link master
Host Link slave
ModbusRTU slave
User defined protocol
Note
The serial port (port 1) CANNOT be used for programming the unit.
4.3.1
Host Link master
If the TJ2-MC64 is the Host Link master, you can send BASIC commands to
a Host Link slave, for example a PC. When you send a BASIC command to
a Host Link slave, the execution of the next BASIC command waits until the
Host Link slave sends a response.
You can use these BASIC commands:
/i
BASIC command
Description
HLM_COMMAND
HLM_COMMAND executes a specific Host Link command to the
slave.
PROGRAMMING MANUAL
BASIC command
Description
HLM_READ
HLM_READ reads data from the Host Link slave to either VR or
TABLE memory.
HLM_STATUS
HLM_STATUS gives the status of the last command of the Host Link
master.
HLM_TIMEOUT
HLM_TIMEOUT defines the Host Link master timeout time.
HLM_WRITE
HLM_WRITE writes data to the Host Link slave from either VR or
TABLE memory.
SETCOM
SETCOM configures the serial communication port and enables the
Host Link protocols.
212