Communication protocols
' Additional settings
result = CAN_CORT(0,9,$2,$2001,1,$f)
tot_result = tot_result AND result
' Node 63
' Set Heartbeat production
result = CAN_CORT(0,9,$63,$1017,0,0,$C8)
tot_result = tot_result AND result
IF tot_result = FALSE THEN
PRINT "Slave Config Settings Fail"
STOP
ENDIF
'----------------------------------------
' Start Network
'----------------------------------------
result = CAN_CORT(0,10)
tot_result = tot_result AND result
IF tot_result = FALSE THEN
PRINT "Start Network Fail"
STOP
ENDIF
NIO = 64
PROGRAMMING MANUAL
4.6.2
Communication status
The TJ1-CORT can give status information to the TJ2-MC64. To retrieve this
status information, use the BASIC command CAN_CORT(unit,4,0). The
result value of this command is given in the table below.
/i
Bit
Value
Description
0
0
Mandatory slave is in correct state
1
Mandatory slave is in unexpected state
1
0
Optional slave is in correct state
1
Optional slave is in unexpected state
2
0
Input data does not contain valid data
1
Input data contains valid data
3
0
No emergency messages received.
1
One or more emergency message received
4
0
No fatal network error
1
Fatal network error
5
0
No PDO length error
1
PDO length error
8
0
No network power problem
1
Network power lost
9
0
No CAN bus problem
1
CAN bus in BUS OFF state
10
0
No duplicate node number in network
1
Duplicate node number in network
12
0
No CAN bus error detected
1
CAN bus error detected