Troubleshooting
6.3
TJ1-PRT
6.3.1
System errors
/i
Indication
Problem
No LEDs are on
The power is off.
or flashing
The TJ1-PRT is defective.
ERH LED is on
Communication failure between
TJ2-MC64 and TJ1-PRT.
ERC LED is on
Unit error. The TJ1-PRT is defec-
tive.
PROGRAMMING MANUAL
Solution
Turn the power on.
Replace the TJ1-PRT.
Reset the TJ2-MC64. If this does
not help, replace the TJ2-MC64.
Replace the TJ1-PRT.
6.3.2
I/O data communication problems
/i
Indication
Problem
COMM LED is off
The PROFIBUS configuration is
and BF LED is on
incorrect, there is no communica-
tion with the master.
The PROFIBUS wiring is not cor-
rect.
You have not properly terminated
the PROFIBUS network.
The PROFIBUS master unit is
defective.
The TJ1-PRT is defective.
Solution
•
Check that the TJ1-PRT has
the same station address as
in the configuration of the
master.
•
Check that no station
address is used twice.
•
Check that the correct pins
of the CN1 connector are
connected.
•
Check that there are no
short circuits or line interrup-
tion.
•
Check that you use the cor-
rect cable type.
•
Check that the stub lines are
not too long.
Terminate the PROFIBUS net-
work at the appropriate places.
Replace the master unit.
Replace the TJ1-PRT.
344