Omron KP100L-OD - 12-2010 User Manual page 97

Gridconnect photovoltaic inverter
Table of Contents

Advertisement

4 Maintenance Operations
E1-6: Islanding active
Situation
Possible Cause
Remedy for User
Remedy for Professional
E1-7: Over voltage instantly (Grid)
Situation
Possible Cause
Remedy for User
Remedy for Professional
4 - 6
Islanding operation detected by active method due to error in the power from the grid.
1. AC connection is not correct.
2. Grid condition is weak or unstable.
3. Other high-power consumption device is affecting the grid system.
4. Inverter is abnormal.
1. If this problem occurs seldom (such as 1 time a day), no action is necessary.
Operation will restart automatically when the grid voltage returns to normal.
If the problem occurs frequently, do the actions below.
2. Find the device with high power consumption near your AC system.
3. Consult your utility power supplier, understand the grid conditions.
4. Ask help of your installer.
1. Check the system connection including polarities and security first.
2. Find the devices with high power consumption near the AC system.
3. Consult the utility power supplier, understand the grid conditions.
4. Use Inverter software to monitor the frequency and voltage.
5. If the situation is not improved, please replace the Inverter.
The grid voltage exceeds 280 V.
1. AC connection is not correct.
2. Grid condition is weak or unstable.
3. Other high-power consumption device is affecting the grid system.
4. Inverter is abnormal.
1. If this problem occurs seldom (such as 1 time a day), no action is necessary.
Operation will restart automatically when the grid voltage returns to normal.
If the problem occurs frequently, do the actions below.
2. Find the device with high power consumption near your AC system.
3. Consult your utility power supplier, understand the grid conditions.
4. Ask help of your installer.
1. Check the system connection including polarities and security first.
2. Find the devices with high power consumption near the AC system.
3. Consult the utility power supplier, understand the grid conditions.
4. Use Inverter software to monitor the frequency and voltage.
5. If the situation is not improved, please replace the Inverter.
Grid Connect Photovoltaic Inverter KP100L-OD- USER'S MANUAL

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Kp100l-od series

Table of Contents