Solar Module
• Do not connect the solar module that has an open-circuit voltage in excess of 850 VDC.
• Do not connect the solar module that require earthing of negative or positive pole.
Breaker
• Use the breaker that corresponds to the capacity of the solar modules for the breaker of the Solar modules
side.
• Use the 20A trip breaker with B or C or D trip characteristics for the breaker of the grid side.
Maintenance - Inspection
• Be sure to inspect install condition, wiring connection, before doing a trial operation.
• To secure the IP65 performance, execute the additional tightening of the cable clamp regularly.
10
Grid Connect Photovoltaic Inverte KP100L-OD-USER'S MANUAL