2 Design
(2)-2 In the case of you use the rubber bush of the five holes type
The rubber bush of five holes is used for connection with five individual cables.
(2)-3 Use the cable and the wire in the table below
The rubber bush for one hole
The rubber bush for five holes
Don't use cables that the loss is more than 1% of nominal power of the inverter.
Refer to the figure below to check possible cable lengths for the different cross-sectional area.
(3) Use the special Rod terminal and crimping pliers for AC wiring like the picture below when connected
with KP100L.
Cross-
sectional area of wire
4 mm
6mm
10 mm
12mm or more
2 - 12
Rubber Bush (five holes)
Diameter of cable
18.5 to 20.5mm
3.5 to 4.0mm
2.0%
4[mm2]
6[mm2]
1.5%
10[mm2]
1.0%
0.5%
0.0%
0
20
40
Cable length [m]
Rod terminal
(Phoenix Contact)
2
AI 4-10 GY
2
AI 6-12 YE
2
AI 10-12 RD
Rod terminal
Cut in 10mm
Grid Connect Photovoltaic Inverte KP100L-OD-USER'S MANUAL
Cap
Cross-sectional area of wire
2
4mm
/ AWG12 or more
2
4mm
/ AWG12
60
80
100
crimping pliers
(Phoenix Contact)
CRIMFFOX 6, CRIMPFOX 10s
CRIMFFOX 6, CRIMPFOX 10s
CRIMPFOX 10s