Omron KP100L-OD - 12-2010 User Manual page 86

Gridconnect photovoltaic inverter
Table of Contents

Advertisement

Items
Sequences during the auto test
(3)
(3-1)The inverter turns on the inside Grid-connected
The Auto
relay
Test of
(3-2)Detect level of OV [L3] is decreased at the point of
OV [L3]
0.5V/s
(3-3)Grid-connected relays are disconnected, when OV
[L3] detect level keeps below the grid voltage for
more than OV [L3] detect time
(3-4)Detect level and detect time of OV [L3] detected in
(3-3) are shown. (Display for ten seconds.)
(4)
(4-1)The inverter turns on the inside Grid-connected
The Auto
relay
Test of
(4-2)Detect level of UV [L1] is increased at the point of
UV [L1]
0.5V/s
(4-3)Grid-connected relays are disconnected, when UV
[L1] detect level keeps above the grid voltage for
more than UV [L1] detect time
(4-4)Detect level and detect time of UV [L1] detected in
(4-3) are shown. (Display for ten seconds.)
Grid Connect Photovoltaic Inverter KP100L-OD- USER'S MANUAL
LCD
AutoTest:OV [L3]
230.03V / 270.00V
The grid voltage of L3
[e.g.] in the case of 230.03V
Setup level of OV [L3]
[e.g.] in the case of 270.00V
Result of OV phase L3
AutoTest:OV [L3]
230.05V /
110ms
Detect level of OV [L3]
[e.g.] in the case of 230.05V
Detect time of OV [L3]
[e.g.] in the case of 110ms
After displaying for ten seconds,
start the auto test of UV [L1]
AutoTest:UV [L1]
230.02V / 184.00V
The grid voltage of L1
[e.g.] in the case of 230.02V
Setup level of UV [L1]
[e.g.] in the case of 184.00V
Result of UV phase L1
AutoTest:UV [L1]
230.04V /
110ms
Detect level of UV [L1]
[e.g.] in the case of 230.04V
Detect time of UV [L1]
[e.g.] in the case of 110ms
After displaying for ten seconds,
start the auto test of UV [L2]
3 Operation
3
9
3 - 23