3 Operation
[13] Setup of Input Signal
When the signal input to "External input signal (AUX_IN)" is turned on, KP100L operates the following table.
MODE
MODE1 (mode of stop)
MODE2 (mode of Gate block)
[14] Error Reset
You can reset occurring error. But error that you can reset is only the error that manual reset is possible.
[Operational Procedure]
At first, after display show the item name of "ErrReset" by you push the "<< "and ">>" key, push the ENT key.
When you push the ENT key and the MODE key at the same time for 5 second after the display became the
execution confirmation "Are you ready?", the Error reset is executed. The display becomes the execution
completion "Executing" after continuing the display executing Error reset for 5 second. After that, the display
returns to the item selection after 3 second pass.
When you push the MODE key while showing the execution confirmation, the display returns to the item selection
without you do Error reset.
Setup:ErrReset
MODE
ENT
Setup:ErrReset
Are you ready?
Push the ENT+MODE key
for 5 second
Setup:ErrReset
Executing
Blinking the Display[3]
After 5 second pass
Setup:ErrReset
Complete
After 3 second pass
3 - 16
When the input is turned on, KP100L stops running.
"Stop" means that Relay turn off and stop power
generation.
When the input is turned on, KP100L does "Gate
block".
"Gate block" means only stop operation of inverter
circuit.
During error occur
ENT
Grid Connect Photovoltaic Inverter KP100L-OD- USER'S MANUAL