Parameters And Menus - Omron E5EK PROGRAMMABLE TYPE User Manual

Digital controller (programmable type)
Table of Contents

Advertisement

1.4 Parameters and Menus

J Parameter types
F Protect mode
F Manual mode
F Level 0 mode
F Program mode
F Level 1 mode
F Level 2 mode
F Setup mode
E5EK-T parameters are distributed between the following ten modes:
Protect mode
Manual mode
Level 0 mode
Program mode
Level 1 mode
Level 2 mode
Setup mode
Expansion mode
Option mode
Calibration mode
The settings of parameters in each of eight modes (excluding the protect
mode and manual mode) can be checked and modified by selection on
the menu display.
The protect function is for preventing unwanted modification of param-
eters, and switching between run and reset operation or auto and
manual operation.
In this mode, the controller can be switched to manual operation. The
manipulated variable can be manipulated manually only in this mode.
Set the controller to this mode during normal operation. In this mode,
you can change the set point and pattern during operation, and execute
step operation (e.g. advance). You can only monitor (not change) the
process value, step No., standby time, pattern elapsing time, pattern
execution count and manipulated variable.
This is the programming mode. In this mode, you can set the number of
steps used in each pattern, pattern execution count, alarm values, set
points for each step, step time, and time signals for two steps.
This is the main mode for adjusting control. In this mode, you can
execute AT (auto-tuning), and set up the control period, PID parame-
ters and heater burnout alarm (HBA) conditions.
This is the auxiliary mode for adjusting control. In this mode, you can
set the parameters for limiting the manipulated variable, switch be-
tween the remote and local modes, and set the loop break alarm (LBA),
alarm hysteresis and the digital filter value of inputs.
This is the mode for setting the basic specifications. In this mode, you
can set parameters that must be checked or set before operation such as
the input type, scaling, output assignments and direct/reverse opera-
tion.
1.4 Parameters and Menus
1--9

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5ek-tE5ek