CHAPTER 3 BASIC OPERATION
Setting Example
1 second min.
1 second min.
1 second min.
3--6
In this example, let's check the input type and temperature units, and
shift the lower limit by 1_C and the upper limit by 3_C.
"input type"
"temperature unit"
"input shift upper limit"= "3.0"
"input shift lower limit" = "1.0"
(1) Select the menu display, and select "
or
keys. For details on selecting the menu display, see page
1-10.
(2) Press the
key for one second minimum to enter the setup
mode. The top parameter in the setup mode "
displayed. This parameter is factory-set to "2: K1".
(3) Press the
key to fix the set value. The display changes to
"
: _C/_F selection" parameter. This parameter is factory-set
to " : _C".
(4) Select the menu display, and select "
or
keys.
(5) Press the
key for one second minimum to enter the level 2
mode. The top parameter in the level 2 mode [
mote" parameter) is displayed.
(6) Press the
key until [
ter) is selected. This parameter is factory-set to "0.0".
(7) Press the
key until "3.0" is displayed.
(8) Press the
key until [
ter) is selected. This parameter is factory-set to "0.0".
(9) Press the
key until "1.0" is displayed. This sets the "input shift
upper limit" and "input shift lower limit" values.
= "2: K1"
= "_C"
: setup mode" using the
: level 2 mode" using the
] ("input shift upper limit" parame-
] ("input shift lower limit" parame-
: input type" is
] ("local/re-