Omron E5EK PROGRAMMABLE TYPE User Manual page 167

Digital controller (programmable type)
Table of Contents

Advertisement

F Calibration:
thermocouple 1
This example describes how to calibrate a thermocouple when the
transfer output function is supported. If the transfer output function is
not supported, skips steps (7) to (10).
(1) When [
] is displayed, the 30-minute timer is displayed on the
No.2 display and counts down. This timer serves as a guide for the
aging time when aging is required.
(2) First, calibrate the main input. Press the
(50 mV calibration display). Set STV output to 50 mV . When the
value on the No.2 display has stabilized (changes of several digits
max.), press the
(3) Press the
key to display [
STV output to 0 mV . When the value on the No.2 display has stabi-
lized (changes of several digits max.), press the [
rarily store the calibration data.
(4) Next, calibrate the cold junction compensator. Press the
display [
] (310 mV calibration display). Set STV output to 310
mV . When the value on the No.2 display has stabilized (changes of
several digits max.), press the
ibration data.
(5) Press the [
] key to display [
Set STV output to 0 mV . When the value on the No.2 display has
stabilized (changes of several digits max.), press the
temporarily store the calibration data.
(6) Finally, calibrate the bias compensation value. Disconnect the STV ,
and enable the thermocouple of the cold junction compensator.
When carrying this out, make sure that the wiring on the STV is
disconnected.
Make sure that the cold junction compensator is set to 0_C and
press the
key. The display changes to [
play for the bias compensation value). When the value on the No.2
display has stabilized (changes of several digits max.), press the
key to temporarily store the calibration data.
(7) Next, calibrate the transfer output function. If the transfer output
function is not supported, skip to step (11). Press the
display changes to [
(8) Set the output to 20 mA by the
the voltage on the digital multimeter. In the example on the left,
the display indicates that the value two digits smaller than before
calibration is "20 mA".
(9) Press the
key. The display changes to [
tion display).
(10) Set the output to 4 mA by the
the voltage on the digital multimeter. In the example on the left,
the display indicates that the value two digits smaller than before
calibration is "4 mA":
(11) Press the
key until the display changes to the date save display.
Press the
key. The No.2 display changes to [
conds later the calibration data is stored to internal memory. If you
press the
key when the No.2 display reads [
tion data is disabled.
(12) This completes calibration of the thermocouple 1 group. Press the
key to return the display to [
7.2 Calibrating Thermocouples
key to temporarily store the calibration data.
] (0 mV calibration display). Set
key to temporarily store the cal-
] (0 mV calibration display).
] (20 mA calibration display).
or
keys while monitoring
or
keys while monitoring
].
key to display [
]
] key to tempo-
key to
key to
] (calibration dis-
key. The
] (4 mA calibra-
], and two se-
], the calibra-
7--5