Setting Example
1 second min.
1 second min.
1 second min.
Alarm 2 is output when the temperature exceeds alarm value 2 pro-
grammed to the SP . Parameter factory settings for "alarm type 2,"
"alarm hysteresis" and "close in alarm/open in alarm" are used.
In this example, the related parameters are set as follows:
"alarm type 2" = "2: upper-limit"
"alarm value 2"
= (set in program setting)
"alarm hysteresis: = "0.02"
"close in alarm/open in alarm"
In this example, let's check the alarm type.
(1) Select the menu display, and select "
the
or
keys. For details on selecting the menu display, see
page 1-9.
(2) Press the
key to enter the setup mode. The top parameter in
the setup mode "
(3) Press the
key until [
played. Default is "2: upper limit".
3.4 Setting Alarm Type
= "
: close in alarm"
: setup mode" pressing
: input type" is displayed.
] ("alarm type 2" parameter) is dis-
3--13