Omron E5EK PROGRAMMABLE TYPE User Manual page 121

Digital controller (programmable type)
Table of Contents

Advertisement

Input type
• Sets the sensor type by the code.
Function
• Set the code according to the following table. Default is "2 : K1 thermocouple".
Set value
Setting
10
11
12
13
14
15
16
17
18
19
20
21
F Related description
3.2 Setting Input Specifications (page 3-4)
F Related parameter
See
When input type is set to temperature input:
"_C/_F selection" (setup mode)
When input type is set to voltage input or current input:
"Scaling upper limit" "Scaling lower limit" "Decimal point" (setup mode)
0
JPt100 -199.9 to 650.0 (_C)
1
Pt100 -199.9 to 650.0 (_C)
2
K1
-200 to 1300 (_C)
3
K2
0.0 to 500.0 (_C)
4
J1
-100 to 850 (_C)
5
J2
0.0 to 400.0 (_C)
6
T
-199.9 to 400.0 (_C)
7
E
0 to 600 (_C)
8
L1
-100 to 850 (_C)
9
L2
0.0 to 400.0 (_C)
U
-199.9 to 400.0 (_C)
N
-200 to 1300 (_C)
R
0 to 1700 (_C)
S
0 to 1700 (_C)
B
100 to 1800 (_C)
W
0 to 2300 (_C)
PLII
0 to 1300 (_C)
4 to 20mA
0 to 20mA
1 to 5V
0 to 5V
0 to 10V
Input Type
/-199.9 to 999.9 (_F)
Platinum resistance thermometer
Platinum resistance thermometer
/-199.9 to 999.9 (_F)
/-300 to 2300 (_F)
/0.0 to 900.0 (_F)
/-100 to 1500 (_F)
/0.0 to 750.0 (_F)
/-199.9 to 700.0 (_F)
/0 to 1100 (_F)
/-100 to 1500 (_F)
/0.0 to 750.0 (_F)
/-199.9 to 700.0 (_F)
/-300 to 2300 (_F)
/0 to 3000 (_F)
/0 to 3000 (_F)
/300 to 3200 (_F)
/0 to 4100 (_F)
/0 to 2300 (_F)
Setup Mode
Thermocouple
Thermocouple
Current input
Current input
Voltage input
Voltage input
5--31

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5ek-tE5ek

Table of Contents