Omron E5EK PROGRAMMABLE TYPE User Manual page 35

Digital controller (programmable type)
Table of Contents

Advertisement

F Event input
10
20
21 22
9
19
8
18
7
17
6
16
5
15
4
14
3
13
2
12
23
1
11
F Transfer output
10
20
21 22
9
19
8
18
7
17
6
16
5
15
4
14
3
13
2
12
23
1
11
F Communications
• Connect event inputs 1 and 2 (EV1/2) to terminal Nos.18 to 20. How-
ever, note that terminal Nos.18 to 20 cannot be used on controllers
supporting the communications function.
• Connect the event inputs as follows:
EV1
20
EV2
19
COM
18
Event input 1 and 2
• Use event inputs under the following conditions:
Contact input
ON: 1 kΩ max., OFF: 100 kΩ min.
No-contact input
ON: residual voltage 1.5 V max.,
OFF: leakage current 0.1 mA max.
• Polarities during no-contact input are as follows:
+
EV1
20
+
EV2
19
COM
18
-
Event input 1 and 2
• Connect transfer output (TRSF) to terminal Nos. 21 and 22.
• The internal equalizing circuit for transfer output is as follows:
4 to 20mA
• Transfer output specifications are as follows:
4 to 20 mA DC, Permissible load impedance: 600 Ω max., Resolution:
Approx. 2600
• Terminal Nos.18 to 20, 21 and 22 can be used only on controllers that
support the communications units (E53-AK01/02/03).
• For details on wiring, see Chapter 6, Using the Communications
Function.
+
+
-
+
21
L
22
-
2.3 Wiring Terminals