Omron E5EK PROGRAMMABLE TYPE User Manual page 139

Digital controller (programmable type)
Table of Contents

Advertisement

Transfer output type
Transfer output upper limit
Transfer output lower limit
• These parameters set the transfer output conditions.
• The "transfer output type" parameter selects one of the following data items as
the transfer output type, and assigns this to transfer output:
Function
Present SP , Process value, Manipulated variable (heat) (standard type), Manipu-
lated variable (cool) (during heating and cooling control on a standard type con-
troller), Valve opening (during position-proportional control)
• The "transfer output upper limit" and "transfer output lower limit" parameters
are used for scaling of transfer output. The setting range varies according to this
output data. Also, a lower limit value larger than the upper limit value may be set.
• Using temperature input, the decimal point position of the present SP or process
value is dependent on the currently selected sensor, and using analog input on the
results of scaling.
• Set the scaling of the present SP or process value within the sensor input indica-
tion range.
"
Setting
"
"
"
"
• Default : [
F Related description
4.11 How to Use Transfer Output (page 4-28)
See
F Option units
E53-AKF
Model
Transfer Output Type
" Present SP
" Process Value
" Manipulated variable (heat)
" Manipulated variable (cool)
" Valve opening
].
Option Mode
Conditions of Use
The transfer output function must be in
use.
Transfer Output Lower Limit to
Transfer Output Upper Limit
-1999 to 9999
-1999 to 9999
-5.0% to 105.0% (standard control), 0.0 to 105.0% (heat-
ing and cooling control)
0.0 to 105.0%
-10.0 to 110.0%
5--49