$UUDQJLQJ PRGXOHV RQ D VLQJOH UDFN
8VH RI RQH RU PRUH UDFNV
You will use either one rack or multiple racks, depending on your planned
application.
5HDVRQV IRU XVLQJ D VLQJOH UDFN
• Compact, space-saving use of all your modules
• Centralized use of your modules
• Fewer signals to be processed
7LS:
If you opt for installation on a single rack, insert a dummy module to the right of the
CPU (order no.: 6ES7 370-0AA01-0AA0). This gives you the option of inserting a
second rack for your application in the future, simply by replacing the dummy
module with an interface module and without having to reinstall and rewire the first
rack.
5HDVRQV IRU XVLQJ PXOWLSOH UDFNV
• More signals to be processed
• Insufficient slots available
5XOHV $UUDQJLQJ PRGXOHV RQ D VLQJOH UDFN
For arranging modules on a single
rack, the following rules apply:
• No more than eight modules (SM, FM, CP) may be installed to the right of the
CPU.
• All modules that you have installed on one rack may not exceed a total current
consumption of 1.2 A (312 IFM: 0.8 A) from the S7-300 backplane bus.
S7-300 Automation System, Hardware and Installation: CPU 312IFM - 318-2 DP
A5E00203919-01
&RQILJXULQJ
5-7