Connecting
6.3 Connecting UC 100
Connect conductors L1, L2, L3
To connect a conductor, proceed as follows:
1. Select an M8-size cable lug for the corresponding conductor cross-section.
2. Strip off the end of the conductor so that the remaining insulation reaches up to the cable lug.
3. Fasten the cable lug correctly to the end of the conductor.
4. If necessary, insulate the cable lug sleeve to maintain the minimum clearances and creepage
distance.
5. Insert the cable lug into the -XL‑2 terminal of the main switch.
6. Insert the connection bolt through the screw holes of the cable lug and terminal.
7. Tighten the fastening nut with the required torque:
6.3.2

Connecting DC cables

To connect the charging station to the DC cable to supply the charge point with power, connect
the DC cable to the DC+ and DC- connectors of the charging station.
Requirements
• You have removed the handle of the main switch.
• You have removed the bottom protective cover.
88
Size of fastening nut
M6
M8
Accessories
-
3VA9153-0QC00
SICHARGE UC 100, UC 200, UC 300, UC 400, UC 600, UC 800
Operating Instructions, 10/2022, A5E50828019-AC
Required tightening torque (±10 %)
8 Nm
20 Nm