Application planning
4.3 Application planning of UC 200
4.3

Application planning of UC 200

4.3.1

Location planning

To operate the charging station safely, you need a location that meets the following
requirements.
Selection criteria for a safe location
Select the location of the charging station so that all actions around charging are always safe.
The user must be able to connect the vehicle without using extension cables. The charging
station, therefore, must be located in the immediate vicinity of the charging areas but without
itself posing a danger to persons or vehicles.
Restricting access
Do not operate the charging station in public areas.
Restrict access to the charging station in the semi-public area, e.g. with a fence.
Figure 4-8
Properties of the base area
To ensure the stability of the charging station, the base area must meet the following
requirements:
• Level
• Dry
• Sufficiently solid and capable of bearing the load (e.g. concrete area in quality class C30/37)
50
Restricting access
SICHARGE UC 100, UC 200, UC 300, UC 400, UC 600, UC 800
Operating Instructions, 10/2022, A5E50828019-AC