 = Connecting cables are included in the scope of delivery
1
The connection power of a control cabinet is 300 or 400 kW.
Planning and mounting
You can install the two control cabinets of the charging station close to one another. Keep the
minimum distance of 10 mm between the two control cabinets.
For planning and mounting, use the specifications of the UC 300/400 charging station for
each control cabinet.
Here is an extract from the specifications in the operating instructions:
• Description of UC 300/400 (Page 32)
• Application planning of UC 300/400 (Page 58)
• Installation of UC 300/400 (Page 78)
• Connecting UC 300/400 (Page 102)
• UC 300/400 maintenance (Page 165)
A.3

Connection of UC 600/800

Connection plan
The following table shows the connection plan between the parent and child control cabinet.
Table A-1
Connection plan between parent control cabinet and child control cabinet
Function
Description
CAN bus
CAN_L
CAN_H
CAN_SHLD
EMERGENCY STOP
K105 input of child
and inputs between
K107 input of child
parent control cabi‐
Door switch contact of
net and
child
child control cabi‐
EMERGENCY STOP input
net
of child
EMERGENCY STOP
EMERGENCY STOP
EMERGENCY STOP
EMERGENCY STOP
A1:EMERGENCY STOP
input of child and parent
A1:Signaling contact in‐
put of child and parent
SICHARGE UC 100, UC 200, UC 300, UC 400, UC 600, UC 800
Operating Instructions, 10/2022, A5E50828019-AC
Parent
-U16:2
-U16:7
-U16:3
-X30:1A
-X30:2A
-X30:3A
-X30:4A
-X30:5A
-X30:6A
-X30:7A
-X30:8A
-X30:10A
-X30:11A
A.3 Connection of UC 600/800
Child
-A3:2
-A3:1
-A3:3
-X30:1A
-X30:2A
-X30:3A
-X30:4A
-X30:5A
-X30:6A
-X30:7A
-X30:8A
-X30:10A
-X30:11A
UC 600/800
Cross-section
2 x 0.22 mm² CAN bus
cable
4 x 0.5 mm²
4 x 0.5 mm²
2 x 0.5 mm²
185