Communication Server 1000M and Meridian 1
Procedure 42
Connecting the shelf 0 FIJI Ring cables (ascending)
Create Fiber Ring 0. Connect the FIJI cards in all Network shelves 0 in
ascending order, from Tx to Rx ports (see
Table 22 on
page
141).
The shortest Fiber Cable must always be used.
The cables from group 0 to group 1 must always be the
same length as the cables from the last group back to
group 0.
The distance between the lengths of each fiber ring from
group 0 to any other group must not exceed 50'. Rings
are directional. Ring 0 is ascending and ring 1 is
descending.
Note: When adding an additional network group, fiber
cables must be changed to adhere to the rules above.
Remove the black cap from the end of each cable before it is connected.
Note: Each end of the NTRC48xx cable is labeled "Tx" or Rx" in the
factory.
1
Start with group 0, shelf 0.
2
Connect a NTRC48xx FIJI Fiber Ring cable of the appropriate length from
the Tx (J1) port of the FIJI card in Group 0, shelf 0 to the Rx (J2) port of
the FIJI card in Group 1, shelf 0.
3
Connect a NTRC48xx FIJI Fiber Ring cable of the appropriate length from
the Tx (J1) port of the FIJI card in Group 1, shelf 0 to the Rx (J2) port of
the FIJI card in Group 2, shelf 0.
4
Continue to connect NTRC48xx FIJI Fiber Ring cables of the appropriate
length from the Tx (J1) port to the Rx (J2) port in shelf 0 of each Network
group. Connect these cables in ascending order of Network groups.
Performing the upgrade
Figure 26 on page 140
IMPORTANT!
81C IGS to CS 1000M MG CP PII FNF Upgrade
Page 139 of 284