Install the CP PII card cage in Core 0
NN43021-469 Standard 01.01 May 2007
Performing the upgrade
Procedure 35
Installing the CP PII card cage in Core 0
1
Check that the card cage is configured as Core 0. See Table 18 on
page 119
for instructions.
2
For AC-powered systems only, install the new MPDU (part of the CP PII
Upgrade kit) to the side on the NT4N40 card cage. The screws that
secure the MPDU are accessible from the power supply slot. See
Figure 20.
Note: Pre-thread 2 bottom mounting screws at the back of the Core/Net
shelf.
3
Check that the power harness at the right rear corner of the card cage has
been transferred from the old card cage to the CP PII card cage.
4
Slide the CP PII card cage halfway into the module.
Figure 20
Location of the screws for the MPDU
MPDU
wall inside
power supply
slot
back plane
MPDU
mounting screws
card cage
553-5890