Address And Main/Sub Setting - Daikin VRV-WIII RWEYQ72PTJU Service Manual

Water cooled heat pump / heat recovery
Hide thumbs Also See for VRV-WIII RWEYQ72PTJU:
Table of Contents

Advertisement

SiUS30-1301
2.3

Address and MAIN/SUB Setting

Introduction
To set the wireless remote controller, you have to set the address for:
 The receiver of the wireless remote controller
 The wireless remote controller.
Setting the Address for the Receiver
The address for the receiver of the wireless remote controller is factory setting to 1. To change this
setting, proceed as follows:
Set the wireless address switch (SS2) on the PCB according to the table below.
When using both a wired and a wireless remote controller for 1 indoor unit, the wired controller
should be set to MAIN. Therefore, set the MAIN/SUB switch (SS1) of the receiver to SUB.
Setting the Address for the Wireless Remote Controller
The address for the wireless remote controller is factory setting to 1. To change this setting,
proceed as follows:
1. Hold down the "
2. Press the "
3. Press the "
4. Press the "
5. Hold down the "
Remote Controller
Unit No.
No. 1
Wireless address
switch (SS2)
MAIN/SUB
MAIN
MAIN/SUB
switch (SS1)
"
" button for at least 4 seconds to get
the Field setting mode.
(Indicated in the display area in the figure at right.)
" button and select a multiple
setting (A/b). Each time the button is pressed the
display switches between "A" and "b".
" button or "
address.
1
2
3
4
Address can be set from 1 to 6, but set it to 1 ~ 3
and to same address as the receiver. (The
receiver does not work with address 4 ~ 6.)
" button to enter the setting.
second to quit the Field setting mode and return to
the normal display.
No. 2
No. 3
SUB
S
S
M
M
" button and the
" button to set the
5
6
" button for at least 1
Wireless Remote Controller
Mode
Address
Multiple
setting
3
2
4
1
5
35