SiUS30-1301
3.41 Transmission Error between Indoor Units and Condensing
Units
U4
Error Code
Applicable
All indoor models
Models
RWEYQ72P, 84P
Method of Error
Micro-computer checks if transmission between indoor and condensing units is normal.
Detection
Error Decision
When transmission is not carried out normally for a certain amount of time
Conditions
Indoor to condensing, condensing to condensing transmission wiring F1, F2 disconnection,
Supposed
Causes
Condensing unit power supply is OFF
System address does not match
Defective condensing unit main PCB
Defective indoor unit PCB
Service Diagnosis
short circuit or wrong wiring
Troubleshooting by Indication on the Remote Controller
219